Surge protector - HSA-275/3+1, Hakel
- Model
- HSA-275/3+1
- Code
- #02971
- Brand
- Hakel
272.56₾
Create account to see your price.
Only a few left
- ✓ Official warranty
- ✓ Delivery across Georgia
- ✓ Card payment or installments
Description
HSA-275/3+1 is a top-quality Type 2+3 (T2+T3) class surge protective device from the Czech brand Hakel. The device provides reliable protection of a three-phase electrical network and the sensitive equipment in it against surge voltages caused by atmospheric events (lightning ⛈️) or industrial switching. 🔌📡
Key advantages:
Thanks to two-stage protection (T2+T3), a single device simultaneously ensures the safety of both the electrical distribution network and the sensitive electronics connected to it (servers, computers, Smart Home systems). Its 3+1 configuration (varistors on the phases and a gas discharge tube on the neutral) is ideal for TT and TN-S systems, as it completely eliminates leakage current to ground. 🛡️💻
Thanks to its fast response time (less than 25 nanoseconds), it instantly discharges excess energy and does not allow the surge current to reach your equipment. ⏱️🚀
Note:
The device has an indicator that allows us to check its status at any time:
🟢 Green means the device is working properly.
🔴 Red means the protection resource is exhausted and it needs to be replaced.
The product fully meets international safety requirements (IEC/EN 61643-11), which ensures its long and reliable operation.
Specifications
| SPD type | T2; T3 |
| Grounding system | TT; TN-S; TN-C-S |
| Number of poles | 4 |
| Rated operating voltage | 230 V |
| Max. operating voltage | 275 V |
| Max. discharge current (8/20) | 50 kA |
| Nominal discharge current (8/20), L/N | 20 kA |
| Nominal discharge current (8/20), L/PE | 20 kA |
| Nominal discharge current (8/20), N/PE | No |
| Total discharge current (8/20), L+N->PE | 50 kA |
| Peak discharge current (10/350), L/N | No |
| Peak discharge current (10/350), L/PE | No |
| Peak discharge current (10/350), N/PE | No |
| Total discharge current (10/350), L+N->PE | No |
| Temporary overvoltage (5 s) | 337 V |
| Response time, L/N | 25 ns |
| Response time, L/PE | No |
| Response time, N/PE | 100 ns |
| Max. backup fuse current (gL/gG) | 160 A |
| Rated current with “V”-type connection | No |
| Max. backup fuse current (gL/gG) with “V”-type connection | No |
| Leakage current | 5 μA |
| Operating temperature | -40 °C - 70 °C |
| Humidity | 5 % - 95 % |
Documents
Related products

Surge protector - HSA-275/2+0, Hakel
HSA-275/2+0
#02970
123.97₾
Only a few left

Surge protector - HSA-275/1+1, Hakel
HSA-275/1+1
#02969
150.10₾
Only a few left

Surge protector - HLSA12,5-275/1+1, Hakel
HLSA12,5-275/1+1
#02961
189.16₾
Only a few left

Surge protector - HLSA12,5-275/2+0, Hakel
HLSA12,5-275/2+0
#02962
197.89₾
Only a few left