Surge protector - HLSA12,5-275/2+0, Hakel

Surge protector - HLSA12,5-275/2+0, Hakel

Model
HLSA12,5-275/2+0
Code
#02962
Brand
Hakel
197.89₾

Create account to see your price.

Only a few left
  • ✓ Official warranty
  • ✓ Delivery across Georgia
  • ✓ Card payment or installments

Description

HLSA12,5-275/2+0 is a top-quality Type 1+2+3 (T1+T2+T3) class combined surge protective device from the Czech brand Hakel. The device provides reliable protection of sensitive equipment in the electrical network against surge voltages caused by atmospheric events (direct lightning strike ⛈️) or industrial switching. 🔌📡 Key advantages: Thanks to its combined protection (T1+T2+T3), this model combines the functions of a lightning arrester and a surge protector. Its 2+0 configuration (two high-power varistors) provides reliable protection of the phase (L) and neutral (N) with respect to ground (PE). This is the best solution for facilities that are equipped with an external lightning rod or receive power via overhead power lines. 🏗️⚡ Thanks to its fast response time (less than 25 nanoseconds), it instantly and safely discharges the high energy caused by lightning and does not allow the surge current to reach your equipment. ⏱️🚀 Note: The device has an indicator that allows us to check its status at any time: 🟢 Green means the device is working properly. 🔴 Red means the protection resource is exhausted and it needs to be replaced. The product fully meets international safety requirements (IEC/EN 61643-11), which ensures its long and reliable operation.

Specifications

SPD typeT1; T2; T3
Grounding systemTN-S; TN-C-S
Number of poles2
Rated operating voltage230 V
Max. operating voltage275 V
Max. discharge current (8/20)50 kA
Nominal discharge current (8/20), L/NNo
Nominal discharge current (8/20), L/PE25 kA
Nominal discharge current (8/20), N/PE25 kA
Total discharge current (8/20), L+N->PE100 kA
Peak discharge current (10/350), L/NNo
Peak discharge current (10/350), L/PE12.5 kA
Peak discharge current (10/350), N/PE12.5 kA
Total discharge current (10/350), L+N->PE25 kA
Temporary overvoltage (5 s)337 V
Response time, L/NNo
Response time, L/PE25 ns
Response time, N/PE25 ns
Max. backup fuse current (gL/gG)160 A
Rated current with “V”-type connectionNo
Max. backup fuse current (gL/gG) with “V”-type connectionNo
Leakage current700 μA
Operating temperature-40 °C - 70 °C
Humidity5 % - 95 %